Stock code:SZ 002334
Current location:Home Solutions Electric Power
Electric Power
Application of Goodrive5000 High Voltage Variable Frequency Speed Regulation System in Induced Draft Fan and Feed Water Pump
Click amount:
Project Overview 

Sinopec thermal power center is equipped with six 25MW coal-fired generating units, the boiler feed pump and induced draft fan respectively adopt 6kV / 2240kW and 6kV / 250kW asynchronous motor drive. During production process, fan and pump are operated in industrial frequency, the flow is adjusted through the fan inlet duct and pump outlet valve, resulting in great energy waste.

Schematic plan


Benefit analysis 
●obvious energy saving




Feed pump operation data

Induced fan operating data

Parameter

industrial frequency

variable frequency

industrial frequency

variable frequency

Input Voltage

6.1kV

6.1kV

5.8kV

5.8kV

Actual running current

220A

140A

31A

23A

Power factor

0.84

0.95

0.83

0.95

Electricity saving ratio

28%

15%

annual electricity saving fee

168.1/1.681 million/set

11.23/0.1123 million/set


Achieve soft starting of motor, without impact current;
Extend equipment maintenance cycle, reduce maintenance workload;
Power factor has been significantly improved.